PVC Insulated Heavy Duty of Design & construction

USP : Heavy duty performance.
: Offers the best combination of safety, efficiency and economy.
Typical Example of Design & Construction As per IS 1554.
Power Cable & Control Cable : Steel round , wire or steel strip armoured.
CONDUCTOR : High conductivity : Grade Copper.
 Insulation : PVC type A or C.
 Inner Sheath : PVC type ST1 or ST2 Galvanized wire steel strip.
 Armour : PVC type ST1 or St2.
IS SPECIFICATION : 8130
: 5831
: 5831
: 3975
: 5831
CORE IDENTIFICATION
:For power cable and control cable upto 4 cores, the cores are identified by different colours as per IS 1554 :
Single Core : Red, Yellow, Blue, Black etc.
2 Core : Red and Black.
3 Core : Red, Yellow and Blue.
½ Core : Red, Yellow, Blue and reduced neutral core in Black.
4 Core : Red, Yellow, Blue and Black.
5Core : Red, Yellow, Blue, Black and Grey.
When the number of core exceed 5, numbering is provided on Black core and 1 core Yellow / Green.
CURRENT RATINGS : The current rating given in tables are based on normal conditions of installation described below.
1. Maximum Conductor 700C for PVC Insulation &Temperature 850C for HRPVC Insulation.
2. Thermal Resistivity of soil 1500C cm/w.
3. Thermal Resistivity of PVC 6500C cm/w.
4. Ground temperature 400C.
5. Depth of laying 75 cms (to the highest point of cable laid direct in the ground).
CLASSIFICATION OF PVC COMPOUND : TYPE Application Max. Conductor Temp.
A Insulation 700C
C Insulation 850C & 1050C
ST1 Sheath 700C
ST1 Sheath 900C
Product Code As per IS 1554 / Part-I / 1998, the product is coded by alphabets :
Aluminum A (No abbreviations are used for copper.)
PVC insulation Y
steel round wire armour W
Steel strip armour F
Steel double round wire armour WW
Steel double strip armour FF
PVC outer sheath Y